linkedintwitterfacebookyoutube
kytola-logo
kytola-logo
Ovald2upgrade

Overview

Model OVAL D2 measuring station is designed to monitor oil flow rates measured by Model SR oval gear meters in oil lubrication systems.

24/7/365 alarming for no-flow, low and high oil flows. The OVAL D2 measuring station can operate as an independent station, connected to Kytola® KVM Control monitoring software or to customer's DCS or PLC. Each OVAL D2 measuring station supports 16, 32, 48 or 64 measuring points. Typical applications are lubrication oil monitoring, industrial oil flow monitoring, and process control monitoring.

Technical data  
Enclosure Painted steel (option: stainless steel AISI 316), IP65
Supply voltage 24 VDC / 0.6 A or 110 - 240 VAC / 50 - 60 Hz
Display 4 x 20 characters + 4 pushbuttons
Communication Modbus RTU or KytolaKVM (RS485 / RS422) protocol
Measuring points / station Max. 64 points with Modbus RTU protocol or max. 48 points with KytolaKVM protocol
Maximum system size In excess of 100 measuring stations and thousands of measuring points in one serial line
Alarm relays 3 potential-free relays for high flow, low flow and very low flow alarms + 1 programmable relay
Alarm inhibition inputs 3 optoisolated inputs to prevent alarms
Sensor types Kytola coil or NAMUR sensor; DIN 19234

Downloads & Support

Download Data SheetContact us

Product key

ovald2 product key

Legal notice & Disclaimer   |  © Kytola All Rights Reserved